Applications
Thermal design for coils, dry coolers and cooling towers
AEON rates heat transfer equipment piece by piece: every tube increment in a coil, every fan and bundle in a condenser, every fill zone in a cooling tower. This page shows, for each type of equipment, what you enter and what you get back.
On this pageHVAC & refrigerationData center coolingPower & process
The method
One method, from a single coil to a complete cooling system
Most rating tools treat a heat exchanger as one block with average conditions. AEON divides it into small pieces and solves each one with its own air and fluid state. Local conditions, and not averages, decide the result.
Every application below is described the same way: what it is used for, what you enter, what AEON calculates, and what the model shows that a block calculation does not.
In the browser
AEON is hosted on Microsoft Azure and used by subscription. There is nothing to install.
Your product data
Tube, fin, fill and fan databases can be extended with your own products.
Results you can pass on
A PDF data sheet for every case, and results as JSON and CSV.
HVAC & refrigeration
Finned coils, rated tube by tube
For manufacturers of coils and air handling units. AEON divides every tube of a coil into increments and solves them along the circuits you define, for water, glycols, brines and refrigerants.
Hot and chilled water coils
Heating and cooling coils in air handling units and ventilation systems, with water, glycol or brine.
You enter
- Air condition at the coil inlet: dry-bulb temperature with wet-bulb temperature or relative humidity, and the air volume flow.
- Site altitude or barometric pressure.
- Fluid, concentration, inlet temperature, pressure and mass flow.
- The coil geometry, tubes and fins (see Common to all coils).
AEON calculates
- Heat transfer rate, compared with the duty you require.
- Sensible and latent heat, with the condensation on the coil when the air is cooled below its dew point.
- Air outlet temperature, relative and absolute humidity, volume flow and face velocity.
- Air-side pressure drop.
- Fluid-side pressure drop and the velocity in the headers.
What the model shows: how your circuiting performs. Each tube is solved in increments along its circuit, so the number of circuits, the tube arrangement and the flow direction show up in both the duty and the pressure drop. The Lacing view displays the circuiting you have defined.
Heat recovery loops (run-around coils) for air handling units
Systems in which a coil in the exhaust air and a coil in the supply air are connected by a glycol loop.
You enter
- Outdoor air and exhaust air conditions and both air volume flows.
- The geometry of the supply air coil and the exhaust air coil, which can differ.
- The loop fluid and its concentration.
- The heat recovery efficiency you require on the supply air side.
AEON calculates
- Both coils and the loop together, in one solution.
- The fluid mass flow at which the supply air coil reaches the required efficiency, or the performance at a mass flow you set.
- Heat recovered and the heat recovery efficiency on the supply and the exhaust side.
- The two loop temperatures.
- Air outlet conditions and air-side pressure drop for each coil, and the fluid-side pressure drop.
- Condensation on the exhaust air coil when the exhaust air is humid enough.
What the model shows: how the two coils depend on each other. A change to one coil shifts the loop temperatures and with them the performance of the other. Rating each coil on its own cannot show this.
Design option: give a fin pitch range and a step size, and AEON finds the design with the lowest mass, which is a good measure of the lowest cost.
DX evaporator coils
Direct expansion coils in air conditioning and commercial refrigeration.
You enter
- Air condition at the coil inlet, air volume flow, and site altitude or barometric pressure.
- The coil geometry, tubes and fins.
- A frost layer thickness, to rate the coil in frosted condition.
- The refrigerant. Any refrigerant in the fluid libraries can be selected, for example R134a, R410A, R32, R290, R717, R1234yf and R1234ze(E).
- The refrigerant-side conditions you know, such as evaporating temperature, superheat or mass flow. AEON accepts any set of values that defines the case without over-specifying it.
AEON calculates
- Cooling capacity, as sensible and latent heat, and the air outlet condition.
- Condensation on the coil, and the air-side pressure drop.
- The refrigerant state at the coil outlet, with all thermodynamic properties.
- Refrigerant-side pressure drop.
What the model shows: how the refrigerant changes along each circuit. Because every tube is solved in increments, the evaporating part and the superheated part of the coil are each calculated with their own heat transfer, and not with one average value.
Condenser coils and steam condensers
Air-cooled refrigerant condensers, and steam coils for air heating.
You enter
- Air condition at the coil inlet, air volume flow, and site altitude or barometric pressure.
- The coil geometry, tubes and fins.
- The refrigerant, selected from the fluid libraries, or steam.
- The conditions you know on that side, such as condensing temperature or pressure, inlet superheat, subcooling or mass flow, in any set that does not over-specify the case.
AEON calculates
- Heat rejected and the air outlet condition.
- Air-side pressure drop.
- The refrigerant or condensate state at the coil outlet, with all thermodynamic properties.
- Pressure drop inside the tubes.
What the model shows: where desuperheating, condensing and subcooling take place along the circuits, since each tube increment is solved with its own refrigerant state.
Transcritical CO2 gas coolers
Gas coolers in CO2 (R744) refrigeration systems and heat pumps.
You enter
- Air condition at the coil inlet, air volume flow, and site altitude or barometric pressure.
- The coil geometry, tubes and fins.
- The CO2 condition at the coil inlet, such as pressure, temperature and mass flow.
AEON calculates
- Heat rejected and the air outlet condition.
- Air-side pressure drop.
- The CO2 state at the coil outlet, with all thermodynamic properties.
- CO2-side pressure drop.
What the model shows: how CO2 behaves above its critical point. There it does not condense; it cools as a dense gas, and its properties change sharply along the tube. AEON solves each tube in increments, so these changes are followed along the circuit and not averaged over the coil.
Common to all coils
Single coils and heat recovery loops use the same input format and the same report.
Geometry
Tubes per row, number of rows and circuits, tube pitches, staggered or inline arrangement, air flow direction and hairpin connections.
Tubes
Diameter, wall thickness, length and internal fouling resistance.
Fins
Plain or corrugated, with thickness, pitch, collar type, contact resistance and external fouling resistance.
Tube and fin materials
Copper, tinned copper, copper-nickel, aluminum, AlMg3, steel, galvanized steel, and stainless steel 304 and 316.
Fluids
Water, ethylene and propylene glycol, ethyl and methyl alcohol, glycerol and ammonia. Brines of calcium, magnesium, sodium and lithium chloride, and of potassium carbonate, acetate and formate.
Fluid properties
Refrigerants from the CoolProp library; glycols and brines from the LibSecRef library (KCE).
Casing
Channel size, frame dimensions and material, and protective coatings.
Report
A PDF data sheet with performance and technical data, including coil mass and internal volume.
Want these calculations inside your own coil selection software, as an API or DLL? Custom calculation engines →
Data center cooling
Heat rejection, rated for the hottest hours
A data center’s heat rejection plant is sized for a few hot hours a year and runs at part load for the rest. AEON rates dry coolers and cooling towers cell by cell across that whole range, so you can see what the plant delivers on the design day and what the fans need on every other day.
Dry coolers and air-cooled heat exchangers
Rejecting heat from the chilled water or facility water loop to ambient air, dry or with adiabatic pre-cooling on hot days.
You enter
- Ambient air temperature and humidity, and site altitude or barometric pressure.
- Fluid (water or a glycol mixture), concentration, inlet temperature and mass flow.
- Finned tubes and bundles: tube rows, tubes per row, tube length and the number of passes.
- The number of bays, with the bundles and fans in each bay.
- The fans, selected from the fan database.
- Optionally, adiabatic pre-cooling of the inlet air by fogging.
- Supply and return piping, for the circulation pump power.
AEON calculates
- Heat rejected and the fluid outlet temperature.
- Air flow and air outlet temperature for each cell.
- The air-side pressure losses, item by item, and the operating point of each fan.
- Fan shaft power and motor power, and the circulation pump power.
- Fluid-side pressure drop through tubes, headers and nozzles.
- With fogging: the air condition after pre-cooling and the water consumption.
- The noise level at a receiver position.
What the model shows: what happens when the cells do not all work alike. Fan speed and fan switching can be set per cell, and a higher air inlet temperature can be given to individual cells to represent warm air recirculating on a crowded roof. The result is the capacity the installation really delivers at high ambient temperature.
Wet cooling towers for the heat rejection loop
Induced-draft cooling towers on the condenser water loop of water-cooled chillers, or for direct heat rejection.
You enter
- Ambient air temperature and humidity, and site altitude or barometric pressure.
- Cooling water flow and inlet temperature, or the cooling range.
- Fill type and dimensions, spray nozzles, and the fan for each cell.
AEON calculates
- The cold water temperature the tower returns, with approach and cooling range.
- Evaporation loss, and the make-up water needed for your cycles of concentration.
- The operating point of each fan, with fan shaft power and motor power.
- Heat and mass transfer for each cell, split into spray zone, fill and rain zone.
- The distribution of the cooling water across the fill, with a check for dry spots.
What the model shows: how part-load operation changes the tower. With fans slowed or switched off cell by cell, AEON shows the cold water temperature you keep and the fan power you save.
For studies of wind and recirculation around a specific building, see Consulting →
Power & process
Large cooling systems, one cell at a time
For manufacturers, EPCs and operators of heat rejection systems at steam power plants, CSP, CHP, petrochemical and process plants. As design and rating software for air-cooled condensers and cooling towers, AEON builds the system from individual fans, bundles and fill zones and gives each cell its own solution.
Forced-draft air-cooled condensers
Direct dry cooling of turbine exhaust steam.
You enter
- Steam condition, as saturated or superheated steam.
- Ambient temperature, humidity and pressure, and wind speed and direction.
- The arrangement of rows and cells, with finned tubes and fans from the databases.
- Settings for individual cells: fan speed or fan off, fouling, and a local air inlet temperature to represent recirculation.
AEON calculates
- Condensing pressure and temperature, the heat rejected, and the steam flow condensed at a given turbine backpressure, compared with the guaranteed flow.
- The steam flow distribution in ducts, headers and tube bundles, at design and off-design conditions.
- Steam backflow and cold zones, with their size and their effect on performance.
- Steam-side pressure drop from the exhaust duct to the bundle outlets, with condenser and dephlegmator bundles reported separately.
- Air flow and fan operating point for each cell, including the natural draft through cells with the fan off.
- The air-side pressure losses, item by item, from the air inlet to the bundle outlet.
- Fan, gearbox and motor power.
- Design checks against recommended limits, such as the flooding risk in the tubes and the ratio of fan area to bundle area.
What the model shows: why a condenser loses performance in wind or with fans out of service. Edge cells and cells near the steam inlet behave differently from the rest, and AEON shows by how much.
Design mode: from the steam condition, the ambient conditions and a preferred fan size, AEON sizes the condenser and returns its main dimensions and performance.
Worked example
A 48-cell air-cooled condenser
8 rows of 6 cells, each with a 9.14 m fan and two rows of elliptical finned tubes. Steam arrives at 19.9 kPa (60.0 °C) with a vapor fraction of 0.94. The air is at 15.6 °C and the site pressure is 84.6 kPa.
What it shows: the target was 412.8 kg/s of steam. At the specified backpressure this condenser takes 395.6 kg/s, which is 95.8% of the target. AEON reports the steam flow you want next to the flow the condenser achieves, so a shortfall is visible at once.
Induced-draft wet cooling towers
Cooling water systems at power and process plants.
You enter
- Ambient air temperature and humidity.
- Cooling water flow, with the inlet temperature or the cooling range.
- Fill type and dimensions, spray nozzles and their placement, and the fan for each cell.
- Settings for individual cells: fan speed or fan off, fouling, and local air inlet conditions.
AEON calculates
- The cold water temperature, with approach, cooling range and Merkel number.
- Evaporation loss, and the make-up water needed for your cycles of concentration.
- Heat and mass transfer for each cell, split into spray zone, fill and rain zone.
- The operating point of each fan, with fan, gearbox and motor power.
- The air-side pressure losses, item by item, from the air inlet to the diffuser.
- The distribution of the cooling water across the fill, from the spray pattern of the nozzles, with a uniformity value and a check for dry spots.
What the model shows: the effect of uneven water distribution. The fill is divided into zones with their own water loading, and the air flow through each zone is solved with it.
Worked example
One induced-draft cell with film fill
A single 15 m by 15 m cell with 1.5 m of film fill and a 10 m fan. It cools 639 kg/s of water entering at 35.7 °C. The air is at 15.5 °C dry-bulb and 11.1 °C wet-bulb, and the site pressure is 84.1 kPa.
What it shows: the fill does 96.7% of the cooling, the spray zone 1.9% and the rain zone 1.4%. AEON reports the three zones separately.
Dry/wet hybrid cooling towers
Cooling towers with a dry section for plume abatement or water saving.
You enter
- The dry section and the wet section, each with its own cells, fans and heat transfer surfaces.
- Ambient conditions, cooling water flow and inlet temperature.
- Fan speeds for the dry and the wet section.
AEON calculates
- The cold water temperature in hybrid and in wet-only operation.
- How the air flows of the dry and the wet section affect each other where they join inside the tower.
- The condition of the mixed air leaving the tower, to judge whether a visible plume can form.
- Fan power for each section.
What the model shows: the lowest fan speeds that still keep the tower free of visible plume, and with them the auxiliary power that can be saved.
Worked example
One hybrid cell with a dry section
A single 15 m by 15 m cell with 2.5 m of trickle fill, eight finned tube bundles with four tube rows each, and a 10 m fan. Water flow and ambient conditions are those of the wet cooling tower example: 639 kg/s entering at 35.7 °C, air at 15.5 °C dry-bulb and 11.1 °C wet-bulb, site pressure 84.1 kPa.
What it shows: 22% of the air passes through the dry section and is heated without taking up water. Mixed with the saturated air from the wet section, it leaves the tower at 82% relative humidity. The further the outlet air is below saturation, the smaller the risk of a visible plume.
These models are also the basis of our performance audits and brownfield studies. Consulting →
Systems
Complete cycles
Components can also be rated as they work together. Besides heat recovery loops, AEON simulates refrigeration cycles, CO2 refrigeration cycles and heat pumps.
Validation
Checked against a real plant
For the hybrid cooling tower at EnBW’s Altbach/Deizisau site, an AEON model predicted the measured cooling water temperatures to within 0.3 °C on average, over 13 operating points in hybrid operation. The original performance curves were off by 6.1 °C for the same data. The work was published in the vgbe energy journal 7·2024.